Hanna Instruments HI-981412-00 GroLine pH dosing system with HI-10063 pH probe

Sale price£347.51 Regular price£365.80
Save £18.29

pH Dosing System is part of Hanna Instruments Groline family and features a pH controller with a peristaltic dosing pump and a process sensor.

HI-981412-00 GroLine pH dosing system with HI-10063 pH probe

Maintaining the correct pH of plant soil or hydroponic nutrient solution is an ongoing task. Macro and micro nutrients, as well as calcium and magnesium bloom boosters, require the correct pH for absorption into the plants root system.

The HI-981412 Groline pH Dosing System, easily assimilates into a nutrient/fertiliser system for soil and hydroponics.

It precisely monitors the pH using the HI-10063 pH/temperature probe and simultaneously controls the addition of acid or base (Up and Down reagents) using On/Off or proportional control to fine tune and maintain the optimum pH.

Growers can define the ideal set point for pH. The HI-981412 is a small dosing controller and can be easily setup for a stand-alone nutrient reservoir or be part of a modular control scheme with the HI-981413 Groline Nutrient Dosing controller.

To obtain a representative sample pH, the probe should be located at a spot that experiences good circulation. The probe can be used in a “sample pot” or reservoir or installed in a flow cell or re-circulation line. Perfect for drain-to-waste or recirculating systems.

Each instrument is delivered in a cardboard box and supplied with:

  • HI-981412-00 without mounting kit
  • HI-10063 pH/temperature probe
  • 4.01 pH Buffer solution, 20 mL (3)
  • 7.01 pH Buffer solution, 20 mL (3)
  • Power connection cable
  • Instrument & electrode quality certificates
  • Instruction manual

Main Benefits

  • Reduced installation time and costs
  • Accessible and easy to maintain pH in a nutrient feeding system
  • The HI-981412 Groline pH Dosing System is engineered to be an inexpensive solution for the horticulturist to have real-time monitoring and control of nutrient solutions to obtain and maintain the ideal pH for optimum results at all times.

Main Features

  • Built-in peristaltic pump with On/Off or Proportional control
  • Manual control for pump priming
  • Overfeed protection using overtime safety timer
  • Resumes dosing on restart in case of power failure
  • Easy to read LCD display with intuitive, color-coded backlight
  • Level input to stop control without reagents
  • Probe detection and recognition
  • Easy to navigate menu to program and adjust settings
  • Wall-mounted design
  • IP65-rated casing

About the HI-10063 Amplified pH/Temperature Probe

The HI-981412 uses the HI-10063 amplified probe that incorporates both pH and temperature sensors and connects to the controller with a single waterproof Quick Connect DIN connector.

The built in amplifier helps to reduce electrical noise from re-circulation pumps to provide for a stable, reliable measurement. The pH glass used is ideal for low conductivity water and provides for fast response.

The PVDF body of the probe has a 1/2” threaded fitting for insertion to an in-line “T” fitting or the flow cell. The back end part of the probe has 3/4” NPT threads for submersion/ tank mounting. The probe body has a hex fitting for tightening snuggly with a wrench.

Specifications

Range 0.00 to 14.00 pH*, -5.0 to 105.0 °C (23.0 to 221.0 °F) * The range may be limited by the probe’s limits.
Resolution 0.01 pH; 0.1 °C (0.1 ºF)
Accuracy @ 25 °C / 77 °F ±0.10 pH; ±0.5 ºC (±0.9 ºF)
Calibration User calibration: automatic, one or two-point with buffer solution (4.01, 7.01, 10.01 pH) Process calibration: single point, adjustable (±0.50 pH around measured pH)
Temperature Compensation Automatic
High or Low Mode Operation Pump Control On/Off control using adjustable set point (4.00 - 10.00 pH) with adjustable hysteresis (0.10 to 1.00 pH)Proportional control using adjustable set point (4.00 - 10.00 pH) with adjustable proportional band (0.10 to 2.00 pH)Startup delay timer at power-on (0 to 600 sec.)Pump flow control 0.5 to 3.5 Litre/hour (0.13 to 0.92 Gallon/hour) and maximum output pressure 1 atm (14 psi)Manual control for pump priming (defined in setup)
pH Alarms High & Low with enable or disable optionTriggered after 5 sec. if the controller records a set of consecutive readings over or under threshold valuesLevel with enable or disable optionOvertime protection (1 to 180 min. or Off)
Controller Alarm System Intuitive alarm system, using red, yellow and green colour coded backlightUser-selectable, alarm setup options
Alarm Relay Output SPDT 2.5A / 230 VacActivated by pH-selectable alarm conditions
Probe Input Quick connect DIN connectorGalvanic isolation
Digital Input External switches can be attached to hold the control due to external events (low reagent level, recirculation pump doesn’t work)Galvanic isolation
Power Supply 100 - 240 Vac, 50/60 Hz
Power Consumption 15 VA
Environment 0-50 ºC (32-122 ºF), max. 95% RH non-condensing
Dimensions 90 x 142 x 80 mm (3.5 x 5.6 x 1.8”)
Weight 908 g (36 oz)
Casing Wall mounted, built-in pump, IP65 rated
HI-10063 pH & temperature probe
Range 0 to 12 pH
Reference Double junction
Junction Cloth
Temperature sensor Yes
Temperature range -5 to 70˚C (23 to 158 °F)
AmpHel® Yes
Matching pin Yes
Body PVDF (white)
Top thread 3/4” NPT
In-line mounting thread 1/2” NPT
Cable length 2 m
Connector Quick connect DIN connector
Maximum pressure @25 °C 3 bar (43.5 psi)
Ordering information
HI-981412-00 supplied with HI-981412 controller, HI-10063 pH/temperature probe, 4.01 pH buffer solution, 20 mL (3), 7.01 pH buffer solution, 20 mL (3), power connection cable, instruction manual and quality certificates for instrument and probe.
HI-981412-10 (with in-line mounting kit) supplied with HI-981412 controller, HI-10063 pH/temperature probe, controller aspiration filter, controller injector, 1/2” thread, saddle for Ø 50 mm pipe (2), PVC aspiration tubing (flexible) (5 m), PE rigid dispensing tubing (5 m), 4.01 pH buffer solution, 20 mL (3), 7.01 pH buffer solution, 20 mL (3), power connection cable, instruction manual and quality certificates for instrument and probe.
HI-981412-20 (+ flow-cell mounting kit) supplied with HI-981412 controller, HI-10063 pH/temperature probe, flow cell for HI-981412, mounting panel assembly for HI-981412, controller aspiration filter, controller injector, 1/2” thread, saddle for Ø 50 mm pipe (3), PVC aspiration tubing (flexible) (5 m), PE rigid dispensing tubing (15 m), barbed tubing adapter 1/2” - 6 mm with racord (2), valves (2), 4.01 pH buffer solution, 20 mL (3), 7.01 pH buffer solution, 20 mL (3), power connection cable, instruction manual and quality certificates for instrument and probe.

Downloads